Portland metro, Oregon · 2026-09-09
Crossdraft truck booth running under velocity in the Portland metro
Truck refinishing shop · GFS / JBI crossdraft truck booth, natural gas heated · Technician: Ben Kurtz
What it was doing
The booth was running under velocity, with spiraling, turbulent air at the top filter banks.
What we found
The pre-intake filters were loaded and starting to collapse, which was dropping the burner's differential pressure. The exhaust filters were loaded too: spray-pattern test shots were being fired onto them. The exhaust pressure gauge had no oil, so nobody could read how loaded the filters were. The intake diffusion media was not fully seated, the exhaust fan carried 1/8 to 1/4 inch of buildup, and a previous technician had bypassed the airflow safety sensors and left them unsealed.
What we did
Performed a burner service during the inspection, then wrote up the repairs in the order to do them: replace the pre-intake and exhaust filters, re-oil and calibrate the pressure gauge or replace it, lubricate the fan and motor, seal the airflow safety sensors and put them back in service, replace the floor sweeps, and convert the lights to LED.
Result and follow-up
The repairs from the report were completed on a follow-up service visit. The inspection called for booth balance and CO levels to be rechecked once the new filters were in.